Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Spyder Model 5 Controllers – Reach New Levels of Functionality and Efficiency

Features

  • “All-in-one” tool with effective workflows providing consistent engineering
  • Integrates with other building systems as part of the Niagara 4 network
  • Automatic creation of customer specific application documentation
  • Batch downloads
  • Fast differential application download
  • Live debugging
  • Auto MAC supporting 64 devices & device identification (push button and bar code)
  • Comes with powerful function block library
  • Relay and Triac outputs
  • IP 30 rating (when used with optional terminal covers)

Product Specifications

Application
Equipment Controller
Used With
WEBS-N4
Comments
WEBS-N4
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL 60730-1, EN61000, and UL916
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Application Size
14 points
I/O Count
14
Output Type
UI, AO, DI, DO
Compatible With
Spyder and Stryker Controllers, WEB-8000
Power Consumption
9 VA
Voltage
24 Vac with a valid range of 20 to 30 Vac
Setpoint Temperature Range (C)
Configurable
Operating Temperature Range (F)
-40 F to 150 F
Operating Temperature Range (C)
0 C to 50 C
Shipping and Storage Temperature Range (F)
-40 F to 158 F
Shipping and Storage Temperature Range (C)
-40 C to 70 C
Approvals, Federal Communications Commission
FCC Part 15, Subpart B, Class B
Approvals, CE
Approved
Approvals, ASHRAE Guidelines
BACnet MS/TP communications as per ANSI / ASHRAE 135-2008
Operating System
WEBs N4
Power Input
24 Vac with a valid range of 20 to 30 Vac
Building Management Interface
Webs-N4
Network Communications
BACnet MSTP
Commissioning Software
Niagara N4 Framework
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.