Controls heating, cooling and space demand oriented economizer operation in the Honeywell Electronic Dual Set point Multizone control system.

Features

  • Controls 3 stages of on/off heating, modulated heating, modulated economizer, 3 stages of on/off cooling and modulated cooling.
  • Responds to highest heating and cooling demand signal from up to 12 T7080 Zone Thermostat/Transmitters.
  • Analyzer is short-circuit protected source of 24 Vdc power for zone thermostat/transmitter, sensor and W7081A Limit Controller Package.
  • Switches all stages off when power is interrupted; switches stages on when power is restored.
  • Compressor turn-on time delays must be incorporated for each compressor.
  • No adjustment or calibrations required.
  • Night setback and cooling shutdown for individual or all zones by addition of time-clock.
  • Mounts with 4 No. 8 Screws (not provided) through holes in base.

Product Specifications

Application
Packaged RTU; Furnace; Split System
Dimensions (in.)
6 1/4 in. high x 4 1/8 in. wide x 2 5/16 in. deep
Dimensions (mm)
159 mm high x 105 mm wide x 59 mm deep
Comments
Load analyzer provides control of On/Off and modulated cooling and modulated economizer functions
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Component Recognized
Approvals, Canadian Standards Association
Component Recognized
Electrical Connections
1/4 in. quick-connect male terminals
Application Size
3 Heat / 3 Cool
Control System
W7080 control system
Compatible With
T7080 Thermostat
Contact Ratings
NO 240 VA inrush @ 24 Vac, 60 VA running @ 24 Vac; NC 75 VA inrush @ 24 Vac, 30 VA running @ 24 Vac
Voltage
24 Vdc
Operating Temperature Range (F)
-40 F to +150 F
Operating Temperature Range (C)
-40 C to +65 C
Shipping and Storage Temperature Range (F)
-40 F to +150 F
Shipping and Storage Temperature Range (C)
-40 C to +65 C
Approvals, Department of Defense Guidelines
Meets
Approvals, ASHRAE Guidelines
Meets ASHRAE 90-75
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.