Overview
VGF Flanged Globe Valves are used for 2-position or modulating control and can be operated by ML6984/7984, ML6420/6425, ML6421/7421 Actuators, MP953 Pneumatic Actuators, Modutrolâ„¢ Motors with Q5001 valve linkage, or MN/MS Direct Coupled Actuators.
Features
- ANSI Class 125 and Class 250 cast iron bodies with flanged end connections.
- Face-to-face flange dimensions per ANSI/ISA S75.03 standard.
- Sizes from 2-1/2 to 6 inches.
- Stainless steel trim standard for long life span.
- Self-adjusting packing.
- Accurate positioning with equal percentage and linear flow characteristics to ensure precise temperature control.
- Universal bonnet for direct-coupled electric and pneumatic actuators for easy mounting, or linkage coupled Modutrolâ„¢ Motors and MN/MS Series direct coupled actuators.
- Constant total flow throughout full plug travel (3-way diverting models).
- Not suitable for combustible gasses.
Product Specifications
- Dimensions (in.)
- 15-3/4 in. lenght x 10 in. width x 12-3/8 in. height
- Dimensions (mm)
- 400 mm lenght x 254 mm width x 314 mm height
- Maximum Safe Operating Pressure (psi)
- 175 psig at 130 F (66 C)
- Maximum Safe Operating Pressure (kPa)
- 1206 kPa at 66 C (130 F)
- Used With
- ML6421B; ML7421B; Q5001/Modutrol IV Motor; MP953
- Comments
- Stem up to close A-AB
- Connection Type
- Flanged
- Body Pattern
- Three-way
- Pipe Size (inch)
- 5 in.
- Pipe Size (DN)
- DN125
- Fluid Temperature (C)
- -7 C to +120 C
- Fluid Temperature (F)
- 20 F to 250 F
- Bonnet Size (in.)
- 1-7/8 in.
- Maximum Differential Pressure Ratings (Close-off) (psi)
- 13 psi
- Maximum Differential Pressure Ratings (Close-off) (kPa)
- 90 kPa
- Capacity (Cv)
- 320 Cv
- Capacity (Kv)
- 275 kvs
- Valve Action
- Mixing, stem up to close A-AB
- Valve Type
- Globe Valve
- Controlled Fluid
- Chilled or hot water with up to 50% Glycol. Not for use with steam or fuels.
- Materials (Body)
- Cast Iron ASTM A126 Class B
- Materials (Seat)
- Stainless Steel
- Materials (Stem)
- Stainless Steel
- Materials (Cartridge)
- Stainless Steel
- Flow Characteristic
- Equal Percentage (A-AB)
- Actuation
- Must be purchased separately
- Static Pressure Rating (psi)
- Meets ANSI 125 Standard
- Static Pressure Rating (kPa)
- Meets ANSI 125 Standard
- ANSI/ASME Rating
- 125
- Stem Travel (in.)
- 1 1/2 in.
- Stem Travel (mm)
- 38 mm
- Bonnet Size (mm)
- 47.6 mm
- Materials (Plug/Ball/Disc)
- Stainless Steel
- Materials (Packing)
- Spring-loaded PTFE cone rings
- Leakage
- Port A seat leakage: 0.5%; Port B seat leakage 1.0%; For Supply mixing control; use diverting value for boiler/chiller bypass
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.