Overview
Solenoid-operated diaphragm valves provide slow opening and fast closing suitable for controlling natural, LP or manufactured gases. They are normally used on atmospheric boilers, commercial water heaters, and rooftop heaters.
Features
- Rated for 150F (66C) maximum temperature applications.
- V48 for line voltage service; V88 for 24Vac service.
- Close firmly with diaphragm that is both weight and spring loaded.
- Two second maximum closing time.
- Valve closes on power failure; recommended for final shutoff service.
- Set opening time with various sized bleed orifices or adjustable bleed valve.
- Use with LP, natural or manufactured gases.
- Made with cast aluminum in straight-through valve pattern.
Product Specifications
- Dimensions (in.)
- 6 13/16 in. high x 5 5/16 in. wide x 5 7/8 in. deep
- Dimensions (mm)
- 173 mm high x 135 mm wide x 149 mm deep
- Materials
- Body--Aluminum
- Item Type
- Product
- Mounting
- Upright (horizontal)
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- File No. MH1639, Guide No. YIOZ
- Approvals, Canadian Standards Association
- Certificate No. 158158-2500005576 (Z21.21-CSA 6.5)
- Electrical Connections
- 6 in. Leadwires
- Power Consumption
- 9 W; 15 VA max
- Voltage
- 24 Vac
- Operating Temperature Range (F)
- 32 F to 150 F
- Operating Temperature Range (C)
- 0 C to 66 C
- Current Ratings
- 0.62 max amps at rated Vac/Hz
- Body Pattern
- Straight-through
- Pressure Ratings (psi)
- 1 psi
- Pressure Ratings (kPa)
- 6.9 kPa
- Type of Fuel
- Natural; LP; Manufactured
- Pipe Size (inch)
- 1 1/4 in.
- Pipe Size (DN)
- DN32
- Bleed Tapping
- 1/8-27 NPT
- Pilot Tapping
- 1/8-27 NPT
- Valve Opening Time
- 5 sec max
- Valve Closing Time
- 2 sec max
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.