Overview
Used for two-position or modulating control of steam and water and glycol solutions (to 50 percent concentration) in heating or cooling systems.
Features
- Sizes range from 1/2 to 2 inches.
- Direct and reverse acting
- High pressure steam models with stainless steel trim
- Spring-loaded, self-adjusting packing.
- Stainless steel stem prevents corrosion.
- Valve designs provide equal percentage characteristics of flow for close control of water, and linear characteristic of flow for close control of steam or chilled water.
- Valves utilize direct mounting, electric or pneumatic linear valve actuators; Q5001 linkage with Modutrol Motor; or Q5020/Q5022A linkages with direct coupled rotary actuators to operate the valve.
- Not suitable for combustible gases.
Product Specifications
- Dimensions (in.)
- 11 5/16 in. high x 5 1/4 in. wide x 4 3/4 in. deep
- Dimensions (mm)
- 287 mm high x 133 mm wide x 120 mm deep
- Maximum Safe Operating Pressure (psi)
- 217 psi at 248 F
- Maximum Safe Operating Pressure (kPa)
- 1500 kPa at 120 C
- Used With
- Q5001/Modutrol IV Motor; MP953; Q5020/DCA; ML6984/ML7984; ML6420,21A,25; ML7420/ML7421A/ML7425
- Ambient Temperature Range (F)
- 36 F to 248 F water
- Ambient Temperature Range (C)
- 2 C to 120 C water
- Connection Type
- Female NPT
- Body Pattern
- Two-way
- Pipe Size (inch)
- 2 in.
- Pipe Size (DN)
- DN50
- Bonnet Size (in.)
- 1-3/8 in.
- Maximum Differential Pressure Ratings (Close-off) (psi)
- 240 psi; For Quiet Water Service--20 psid
- Maximum Differential Pressure Ratings (Close-off) (kPa)
- 1655 kPa; For Quiet Water Service--138 kPa
- Capacity (Cv)
- 46.8 Cv
- Capacity (Kv)
- 40 kvs
- Valve Action
- Stem down to close
- Valve Type
- Globe Valve
- Controlled Fluid
- Chilled or hot water with up to 50% Glycol or Steam. Not for use with fuels.
- Materials (Body)
- Red Brass
- Materials (Seat)
- Stainless Steel
- Materials (Stem)
- Stainless Steel
- Materials (Cartridge)
- Brass
- Flow Characteristic
- Equal Percentage
- Actuation
- Must be purchased separately
- Static Pressure Rating (psi)
- Meets ANSI 150 Standard
- Static Pressure Rating (kPa)
- Meets ANSI 150 Standard
- ANSI/ASME Rating
- 150
- Stem Travel (in.)
- 3/4 in.
- Stem Travel (mm)
- 20 mm
- Bonnet Size (mm)
- 35 mm
- Materials (Plug/Ball/Disc)
- Brass
- Materials (Packing)
- Teflon
- Leakage
- Seat: 0.05% of Cv
- Approvals, CRN Number
- 0C0861.9087YTN/0C0861.108
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.