Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

One-pipe, single temperature, low-capacity pneumatic thermostat used to provide proportional control of pneumatic valves and mixing boxes in heating and air conditioning systems. It mounts in a slot or light troffer diffuser or a return air grill.

Features

  • Two-way setpoint indicator for vertical or horizontal mounting.
  • Detents in 1 F (0.5 C) increments for blind operation.

Product Specifications

Application
Single temperature, low capacity, pneumatic thermostat
Airflow Usage
0.011 scfm (5.2 mL/s)
Dimensions (in.)
1 in. high x 2 1/2 in. wide x 1 1/8 in. deep
Dimensions (mm)
25 mm high x 63 mm wide x 27 mm deep
Maximum Safe Operating Pressure (psi)
30 psi
Maximum Safe Operating Pressure (kPa)
207 kPa
Temperature Range (F)
150 F maximum
Temperature Range (C)
66 C maximum
Comments
Requires external 0.005 in. restrictor
Mounting
Wall mount
Setpoint Temperature Range (C)
15 C to 30 C
Setpoint Temperature Range (F)
59 F to 86 F
Shipping and Storage Temperature Range (F)
150 F maximum
Shipping and Storage Temperature Range (C)
66 C maximum
Sensor Element
Bimetal
Throttling Range (F)
2 F to 10 F
Throttling Range (C)
1 C to 5 C
Action
Direct Acting
Setpoint
Single
Number of Pipes
1
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.