Overview
One-pipe, single temperature, low-capacity pneumatic thermostat used to provide proportional control of pneumatic valves and mixing boxes in heating and air conditioning systems. It mounts in a slot or light troffer diffuser or a return air grill.
Features
- Two-way setpoint indicator for vertical or horizontal mounting.
- Detents in 1 F (0.5 C) increments for blind operation.
Product Specifications
- Application
- Single temperature, low capacity, pneumatic thermostat
- Airflow Usage
- 0.011 scfm (5.2 mL/s)
- Dimensions (in.)
- 1 in. high x 2 1/2 in. wide x 1 1/8 in. deep
- Dimensions (mm)
- 25 mm high x 63 mm wide x 27 mm deep
- Maximum Safe Operating Pressure (psi)
- 30 psi
- Maximum Safe Operating Pressure (kPa)
- 207 kPa
- Temperature Range (F)
- 110 F maximum
- Temperature Range (C)
- 43 C maximum
- Comments
- Requires external 0.005 in. restrictor
- Mounting
- Wall mount
- Setpoint Temperature Range (F)
- 67 F to 83 F
- Shipping and Storage Temperature Range (F)
- 150 F maximum
- Shipping and Storage Temperature Range (C)
- 66 C maximum
- Sensor Element
- Bimetal
- Throttling Range (F)
- 2 F to 10 F
- Throttling Range (C)
- 1 C to 5 C
- Action
- Direct Acting
- Setpoint
- Single
- Number of Pipes
- 1
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.