Overview

One- or two-pipe direct-acting temperature sensor used with RP908/RP920 Controllers to provide proportional control of pneumatic valve and damper actuators.

Features

  • Plug-in air connections.
  • High efficiency air filter.
  • Bimetal element.
  • Continuous temperature indication available by using receiver gage.

Product Specifications

Application
Temperature Sensor
Airflow Usage
0.019 scfm (9 mL/s)
Dimensions (in.)
3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
Dimensions (mm)
83 mm high x 51 mm wide x 41 mm deep
Maximum Safe Operating Pressure (psi)
25 psi
Maximum Safe Operating Pressure (kPa)
170 kPa
Comments
Order Cover Separately
Mounting
Vertical or Horizontal Wall Mounting
Sensor
Bimetal
Operating Temperature Range (F)
110 F Maximum
Operating Temperature Range (C)
43 C Maximum
Pressure Ratings (psi)
Output--3 psi to 15 psi; Supply--16-25 psi
Pressure Ratings (kPa)
Output--21 kPa to 103 kPa; Supply--110 to 172 kpa
Action
Direct Acting
Number of Pipes
1 or 2
Sensor Range
50 F to 100 F; 10 C to 38 C
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.