Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

The TH114 Series delivers the features that matter most in a non-programmable thermostat: an easy-to-read backlit display, slim contemporary design and precise temperature control.

Features

  • Three choices of temperature control in a single thermostat (Ambient, Floor, or Ambient with Floor temperature limits)
  • 5 mA ground fault circuit interrupter (GFCI) on GA models
  • 15 mA equipment ground fault protection devices (EGFPD) on GB models
  • GFCI and EGFPD test light verifies safety control is functioning properly and alerts if a leak is detected
  • Advanced temperature control ensures total comfort by minimizing temperature swings
  • ON/STANDBY switch enables thermostat shutdown at the end of heating season for added security
  • On-screen heating power indicator gives at-a-glance verification of power being used
  • Backlit display
  • Battery-free

Product Specifications

Application
Radiant floor; Baseboard heater; Radiant ceiling; Convector or Fan-forced Heater; Electric Heating
Dimensions (in.)
4.89 in. X 2.76 in. X 0.91 in.
Dimensions (mm)
124 mm X 70 mm X 23 mm
Includes
15-ft floor sensor
Used With
Aube RC840/RC840T Series Electromechanical Relays
Comments
Backlight; On/Standby switch; Remote input for telephone controller (Unoccupied input); Min. and max. floor temperature limits in AF mode; 15-minute cycles
Mounting
Vertical
Electrical Ratings
0.5 A / 24 VAC
Approvals, Canadian Standards Association
Approved; Compliant to CAN/CSA-C828-06
Customer Special
Klimatrol
Electrical Connections
6 in. (150 mm) tinned copper lead wires
Supply Voltage
0.5 A, 24 VAC
Switch Positions (System)
°C/°F; AF/F
Operating Temperature Range (F)
32 F to 122 F
Operating Temperature Range (C)
0 C to 50 C
Power Method
Hardwired
Sensor Element
Thermistor
Accuracy (F)
± 0.9 F
Accuracy (C)
± 0.5 C
Differential Temperature (F)
1 F
Differential Temperature (C)
0.5 C
Color
White
Ambient Temperature Range (F)
AF mode: 32 F to 122 F; F mode: 32 F to 140 F
Ambient Temperature Range (C)
AF mode: 0 C to 50 C; F mode: 0 C to 60 C
Switch Type
External electromechanical relay
Terminal Designations
R, C, W
Temperature Control Mode Selections
AF for Ambient & Floor; "F" for Floor
Setting Temperature Range (F)
AF mode: 40 F to 86 F; F mode: 40 F to 104 F
Setting Temperature Range (C)
AF mode: 5 C to 30 C; F mode: 5 C to 40 C
Cycles per Hour
4 CPH
Parts Needed for Operation (not included)
Aube RC840/RC840T Series Electromechanical relays
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.