Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

The T7771A Remote Temperature Sensors are direct wired wall modules for use with the Honeywell T7350 Commercial Programmable Thermostat. The T7771A has a space temperature sensor, LED push button setpoint adjustment, and override with LED.

Features

  • Push button setpoint adjustment with LED indicators.
  • Occupied/unoccupied override (bypass) with LED.
  • LONWORKS® bus jack.
  • Operating range 45 to 99°F (7 to 37°C).

Product Specifications

Application
Remote Room Temperature Sensor for use with T7350 thermostat
Dimensions (in.)
5 1/32 in. high x 3 5/32 in. wide x 1 in. deep
Dimensions (mm)
128 mm high x 80 mm wide x 25 mm deep
Used With
T7350
Comments
Can be configured to output 10K ohms for use in multiple sensor averaging with T7770A.
Item Type
Product
Mounting
Mounted on a standard 2 x 4 inch junction box or on a 60 mm diameter junction box.
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Sensor
20 K ohm NTC non-linear
Setpoint Temperature Range (C)
offset ± 1.67 C
Setpoint Temperature Range (F)
offset ±3F
Operating Temperature Range (F)
45 F to 99 F
Operating Temperature Range (C)
7 C to 37 C
Shipping and Storage Temperature Range (F)
-40 F to +150 F
Shipping and Storage Temperature Range (C)
-40 C to +65 C
Network Communications
LonWorks Bus
Color
White
Approvals, N.E.C.
Class II
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.