Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Line Voltage Temperature Controllers that provide ON-OFF temperature control utilizing two liquid filled capillary tubes that make two SPST switches that open on a temperature rise.

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
Tobacco curing control
Dimensions (in.)
5 3/4 in. high x 2 in. wide x 2 1/8 in. deep
Dimensions (mm)
146 mm high x 51 mm wide x 57 mm deep
Item Type
Product
Frequency
50 Hz; 60 Hz
Contact Ratings
120 Vac-- 7.4 AFL, 44.0 ALR; 240 Vac-- 5.1 AFL, 30.6 ALR
Voltage
120 Vac; 240 Vac
Setpoint Temperature Range (C)
4 C to 82 C
Setpoint Temperature Range (F)
40 F to 180 F
Operating Temperature Range (F)
125 F Maximum
Operating Temperature Range (C)
52 C Maximum
Output
relay
Relay Outputs
2 SPST
Sensor Inputs
1
Sensor Element
Copper bulb
Capillary Length (ft)
10 ft
Capillary Length (m)
3 m
Bulb Size (in.)
28 in. long x 1/8 diameter
Bulb Size (mm)
711 mm long x 3 mm diameter
Differential Temperature (F)
5 F
Differential Temperature (C)
3 C
Interstage Differential Temperature (C)
4 C
Interstage Differential Temperature (F)
7 F
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.