Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Provides SPDT heavy-duty, line-voltage temperature control in ventilation, heating or cooling systems.

Features

  • Use in a variety of farm, industrial or commercial applications.
  • Wall or duct mount in any position.
  • Fast response, tin-plated element not affected by adverse environment.
  • Rugged case.
  • Mounts on flat surface with three screws.
  • T6064 provides fast response with hydraulic temperature sensing elements mounted on the unit.

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
Provides control in heating systems
Dimensions (in.)
7 5/8 in. high x 2 5/8 in. wide x 2 in. deep
Dimensions (mm)
194 mm high x 67 mm wide x 51 mm deep
Comments
Make R to B on temperature fall
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Listed: E4436, vol. 5, sec. 12, Guide XAPX
Approvals, Canadian Standards Association
CSA Listed: Report -1
Contact Ratings
120 Vac-- 16.0 AFL, 96.0 ALR; 240 Vac-- 8.0 AFL, 48.0 ALR
Voltage
120 Vac; 240 Vac
Setpoint Temperature Range (C)
2 C to 38 C
Setpoint Temperature Range (F)
36 F to 100 F
Operating Temperature Range (F)
125 F Maximum
Operating Temperature Range (C)
52 C Maximum
Output
relay
Relay Outputs
1 SPST
Sensor Inputs
1
Sensor Element
Fast response capillary
Accuracy (F)
±6 F
Accuracy (C)
±3.3 C
Differential Temperature (F)
3.5 F
Differential Temperature (C)
1.9 C
Color
Gray
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.