Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

A three-port relay averages the signals from two thermostats to control a single device such as a heating coil valve for a multizone unit. Replacements available for Johnson, Powers, Robertshaw, Barber-Colman, and olderHoneywell models

Features

  • In-line, wall or panel mounted.
  • Sharp-barb air connections.
  • Molded plastic construction.

Product Specifications

Application
Pneumatic Three-Port Averaging Relay
Airflow Usage
0.007 scfm (3.303 mL/s) maximum
Dimensions (in.)
1 1/2 in. high x 7/8 in. wide x 15/16 in. deep
Dimensions (mm)
38 mm high x 22 mm wide x 24 mm deep
Maximum Safe Operating Pressure (psi)
30 psi, maximum
Maximum Safe Operating Pressure (kPa)
205 kPa, maximum
Temperature Range (F)
32 F to 125 F
Temperature Range (C)
0 C to 52 C
Mounting
Wall or In-line or panel
Operating Humidity Range (% RH)
5 to 95% RH
Pressure Range (psi)
Input Operating--3 to 15 psi; Output Operating --3 to 15 psi
Pressure Range (kPa)
Input Operating--21 to 103 kPa; Output Operating --21 to 103 kPa
Air connections
Barb fittings 5/32 in. (4 mm) O.D. plastic tubing
Capacity
0.039 scfm at 1 psi differential (18 mL/s at 5 kPa differential)
Operation
Output pressure equals average of two input pressures
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.