Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Pneumatic relay produces a modulating pressure output, and controls pneumatic valve or damper actuators in sequence from a single thermostat. Replacements are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.

Features

  • Adjustable pilot start point pressures.
  • Two pilot pressure spans available.
  • Four sharp-barb air connections.
  • Molded plastic construction with neoprene.
  • Mounting clip provided.

Product Specifications

Application
Pneumatic, Four Port Ratio Relay
Airflow Usage
0.002 scfm (1.0 mL/s) maximum
Dimensions (in.)
2 in. diameter x 2 5/8 in. deep
Dimensions (mm)
52 mm dia. x 67 mm deep
Maximum Safe Operating Pressure (psi)
30 psi, maximum
Maximum Safe Operating Pressure (kPa)
205 kPa, maximum
Temperature Range (F)
0 F to 140 F
Temperature Range (C)
-18 C to +60 C
Includes
14003030-002 Mounting Clip and scaleplate with psi markings
Mounting
Wall or In-line or panel
Operating Humidity Range (% RH)
5 to 95% RH
Pressure Range (psi)
Output Span--3 to 13 psi; 5 psi pilot input span
Pressure Range (kPa)
Output Span--21 to 90 kPa; 34 kPa pilot input span
Action
Direct Acting
Air connections
Barb fittings, Port 1: 1/4 in. (6 mm) O.D. plastic tubing; Other Ports: 5/32 in. (4 mm) O.D. plastic tubing
Capacity
0.039 scfm at 1 psi differential (18 mL/s at 5 kPa differential)
Operation
Produces modulating pressure output proportional to pilot pressure input changes
Pilot Start Pressure (psi)
Adjustable 0 to 10 psi
Pilot Start Pressure (kPa)
Adjustable 0 to 69 kPa
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.