Overview
Electrically operated pneumatic switches used to interlock an electrical system and a pneumatic control system. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell devices.
Features
- Usable as a diverting relay, a selector relay, or a stop and bleed relay.
- Mount and operate in any position.
- Available with lead wires or junction box.
- Line or low voltage models available.
Product Specifications
- Application
- Electric / Pneumatic Relay
- Airflow Usage
- 0.42 scfm (200 mL/s) at 20 psi (138 kPa) supply with 1 psi (7 kPa) pressure drop
- Dimensions (in.)
- 2 7/8 in. high x 3 13/16 in. wide x 1 1/4 in. deep
- Dimensions (mm)
- 73 mm high x 97 mm wide x 32 mm deep
- Maximum Safe Operating Pressure (psi)
- 50 psi, maximum
- Maximum Safe Operating Pressure (kPa)
- 340 kPa, maximum
- Temperature Range (F)
- 0 F to 100 F
- Temperature Range (C)
- -18 C to +38 C
- Includes
- Junction Box
- Mounting
- Surface
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- Component Recognized File: MP1502, Vol. 11, Sec. 1,UL Listed: Guide Y10Z
- Approvals, Canadian Standards Association
- Listed: File No. LR50900
- Electrical Connections
- Junction Box and 15 in. (380 mm) leads
- Operating Humidity Range (% RH)
- 5 to 95% RH
- Voltage
- 110 Vac at 50 Hz; 120 Vac at 60 Hz
- Approvals, Canadian Underwriters Laboratories Inc.
- Listed: File No. LR50900
- Air connections
- Barbed fitting for 1/4 in. O.D. plastic tubing
- Capacity
- 0.075 Cv minimum
- Operation
- Energized: ports 1 and 3 connected, port 2 blocked,De-energized: ports 2 and 3 connected, port 1 blocked
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.