Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

The Honeywell R7140G, L, M Burner Control Modules are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications.

Features

  • Functions provided by the R7140G,L,M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
  • Upgrade replacement for BC7000 or R4140 legacy Programmer controls.
  • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.

Product Specifications

Application
Upgrade Replacement Programming Control for R4140 or BC7000
Dimensions (in.)
7 in. wide x 6 5/32 high x 5 3/4 in. deep
Dimensions (mm)
177 mm wide x 156 mm high x 146 mm deep
Weight (lb)
3 lb 1 oz
Weight (kg)
1.4 kg
Comments
LHL-LF Proven
Frequency
50 Hz; 60 Hz (±10%)
Approvals, Underwriters Laboratories Inc.
Component Recognized, File No. MP268; Guide No. MCCZ.
Voltage
120 Vac (+10, -15%)
Shipping and Storage Temperature Range (F)
-40 F to +140 F
Shipping and Storage Temperature Range (C)
-40 C to +60 C
Approvals, Federal Communications Commission
FCC Part 15, Class B, Emissions.
Flame Establishing Period - Pilot
4 sec or 10 sec
Flame Establishing Period - Main
10 sec, or 15 sec, or 30 sec, or Intermittent
Interlocks
Running
Preignition
Yes
PrePurge
Determined by ST7800A Purge Timer Card
PostPurge
15 sec
Early Spark Termination
Yes, 5 sec
Required Components
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card.
AirFlow Check
User selectable
Second Stage Pilot Valve
selectable
Pilot Type
Interrupted or Intermittent
Vibration
0.5 G environment
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.