Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

The P7911C PressureTrol® Controller is a line voltage pressure controller for pressure systems up to 300 psi (206 kPa). The P7911C provides On/Off Control, High Limit and 4 to 20 mA pressure valu

Features

  • Use only with steam, air or noncombustible gases that do not corrode the pressure sensing element.
  • Models available in 15, 150 and 300 psi (103, 1034 and 2069 kPa) maximum setpoints .
  • Light Emitting Diode (LED) indicators show power, call for heat function and lockout status. .
  • Clear cover allows setpoint and differential to be read, but not adjusted without opening the cover..
  • Manual reset possible without opening the cover. .
  • Electronic maximum fixed stop limit..

Product Specifications

Application
On-Off and Limit Control plus Pressure Sensor
Dimensions (in.)
5 1/4 in. high x 4 21/32 in. wide x 3 3/8 in. deep
Dimensions (mm)
133 mm high x 119 mm wide x 86 mm deep
Used With
R7911 Sola Steam Controller
Materials
Case: Plastic
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Listed: File No. MP466, Vol 30, Sec 1
Approvals, Canadian Standards Association
Certified: Certificate 1355621 (LR095329)
Electrical Connections
Screw terminals
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Contact Ratings
120 Vac Switch Contact-- 9.8 AFL, 58.8 ALR, 10.0 A resistive
Power Consumption
3.6 W, 4.7 VA @ 50Hz; 3.3 W, 4.0 VA @ 60 Hz
Voltage
120 Vac
Operating Temperature Range (F)
32 F to 140 F
Operating Temperature Range (C)
0 C to +60 C
Approvals, Factory Mutual
Approved: Certificate 3018936
Sensor Element
Stainless Steel, solid state sensor
Operating Range (psi)
0 to 150 psi; 225 psi - Maximum Sustained
Operating Range (kPa)
0 to 1034 kPa; 1151 kPa - Maximum Sustained
Switching Action
Break on pressure rise
Pipe Connection
Main or High Pressure--1/2 in. NPT internal thread
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.