Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Pneumatic-electric switches convert a controller's pneumatic signal to electrical switching, providing start and stop control. Replacements available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic/ electric switches.

Features

  • Models available for surface or panel mounting.
  • Barb protected by open cage.
  • All ferrous parts plated to prevent corrosion.
  • Factory calibrated setpoint field adjustable to meet job requirements.
  • Neoprene diaphragm element.

Product Specifications

Application
Pneumatic / Electric Switch
Dimensions (in.)
3 1/4 in. high x 2 7/8 in. wide x 1 1/2 in. deep
Dimensions (mm)
83 mm high x 73 mm wide x 38 mm deep
Maximum Safe Operating Pressure (psi)
30 psi, maximum
Maximum Safe Operating Pressure (kPa)
207 kPa, maximum
Temperature Range (F)
40 F to 140 F
Temperature Range (C)
4 C to 60 C
Comments
No Factory Calibration
Mounting
Panel, through double D hole secured with hex nut
Frequency
60 Hz
Approvals, Underwriters Laboratories Inc.
Category SDFY or SDFY2
Electrical Connections
1/4 in. quick-connect male terminals
Operating Humidity Range (% RH)
5 to 95% RH, 80 F (27C) max wet bulb
Approvals, Canadian Underwriters Laboratories Inc.
Listed, Volume I
Differential Pressure Range (psi)
1 psi
Differential Pressure Range (kPa)
7 kPa
Switch Operation
Converts pneumatic signal to electrical switching action (SPDT)
Switching Action
Make COM-NO on pressure rise to setpoint plus differential,Make COM-NC on pressure fall to setpoint
Pilot Duty Ratings
720 VA @ 125, 250 or 277 Vac
Switch Type
Pneumatic/Electric Switch
Air connections
Barb fitting for 1/4 in. (6 mm) O.D. plastic tubing
Setpoint Range (psi)
Field Adjustable--2 to 17 psi
Setpoint Range (kPa)
Field Adjustable--14 to 117 kPa
Motor Load
3/4 hp @ 125, 250 or 277 Vac
Resistive Load
25A @ 125, 250 or 277 Vac; 10A @ 480 Vac
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.