Overview
Honeywell's Fast-Acting, Two-Position Actuators are line volt (230V), 30 lb-in., spring return direct coupled actuators (DCA) for Fire and Smoke dampers (on/off control). The actuator accepts an on/off signal from a single-pole, single-throw (SPST) controller. Reversible mounting allows actuator to be used for either clockwise (cw) or counterclockwise (ccw) spring rotation.
Features
- 30 lb-in. (3.4 N•m) minimum driving torque at 350 F (176 C).
- Reversible mounting facilitates use in either clockwise (cw) or counterclockwise (ccw) spring rotation
- Integral spring return ensures level of return torque
- Fifteen-second spring return timing
- No special cycling required during long-term holding
- No audible noise during holding
- Patent pending design eliminates need for limit switches to reduce power consumption
- Ninety-five degree angle of rotation
- Actuator holds rated torque at reduced power level
- Die-cast aluminum housing
- Housing design allows flush mounting to damper
- Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350 F
- Models available with SPST position-indicating switches (7 degree, 85 degree stroke)
Product Specifications
- Application
- Fire and Smoke
- Dimensions (in.)
- 8.9 in high x 5.13 in wide x 3.32 in deep
- Dimensions (mm)
- 227 mm high x 129 mm wide x 84 mm deep
- Weight (lb)
- 5 lb
- Weight (kg)
- 2.3 kg
- Materials
- Aluminum housing
- Comments
- Two integral 3/8 in. clip-in flexible conduit connections
- Item Type
- Product
- Mounting
- Direct Coupled
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL873, Plenum Rated
- Electrical Connections
- Color-coded leads
- Operating Humidity Range (% RH)
- 5 to 95% RH, non-condensing
- Supply Voltage
- 230 Vac ±10%
- Power Consumption
- Driving-- 0.13A, 18W, Holding-- 0.10A, 11W
- Shipping and Storage Temperature Range (F)
- -40 F to 140 F
- Shipping and Storage Temperature Range (C)
- -40 C to +60 C
- Approvals, Canadian Underwriters Laboratories Inc.
- cUL C22.2 No. 24-93
- Ambient Temperature Range (F)
- 0 F to +130 F
- Ambient Temperature Range (C)
- -18 C to +55 C
- Approvals, C-Tick
- N314
- Environmental, Electrical or Ingress Protection Rating
- NEMA 1, IP40
- Internal Auxiliary Switch
- 0
- Maximum Noise Rating
- Driving (dB(A) @ 1m)-- 80; Holding (dB(A) @ 1m)-- 20 (no audible noise)
- Stroke
- 95 ±3 degrees
- Shaft Dimensions (in.)
- 1/2 in. round
- Actuator Type
- Damper
- Control Signal
- Two position; SPST
- Fail Safe Mode
- Spring Return
- Torque Rating (lb-in.)
- 30 lb-in.
- Torque Rating (Nm)
- 3.4 Nm
- Spring Return Torque/Force (lb-in., lbf)
- 30 lb-in.
- Spring Return Torque/Force (Nm, N)
- 3.4 Nm
- Additional Torque Ratings (lb-in.)
- Maximum Stall-- 150 lb-in.; Minimum Driving at 350 F-- 30 lb-in.
- Additional Torque Ratings (Nm)
- Maximum Stall-- 17 Nm; Minimum Driving at 175 C-- 3.4 Nm
- External Auxiliary Switches Available
- No
- Timing, Nominal
- Driving @ 60 Hz-- 15 sec
- Spring Return Timing
- 15 sec
- Shaft Adapter Type
- Aluminum Hub, two set screws
- Shaft Dimensions (mm)
- 13 mm round
- Spring Return Direction
- By orientation
- Electrical Connections (in.)
- 32 in.
- Electrical Connections (mm)
- 0.8 m