Product Specifications

Application
HVAC
Dimensions (in.)
9.72 in high x 3.94 in wide x 2.95 in deep
Dimensions (mm)
247 mm high x 100 mm wide x 75 mm deep
Includes
Mounting bracket, self-centering shaft adapter, 3mm crank
Weight (lb)
6 lb
Weight (kg)
2.72 kg
Materials
Aluminum housing, Plenum rated plastic access cover
Comments
Integral 1/2 in. NPSM conduit connection
Mounting
Direct Coupled
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL873, Plenum Rated
Electrical Connections
Enclosed screw terminal strip (22 to 14 AWG)
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Supply Voltage
24 Vac or Vdc
Power Consumption
Driving-- 16 VA, Holding-- 5 VA
Operating Temperature Range (F)
-40 F to +140 F
Operating Temperature Range (C)
-40 C to +60 C
Shipping and Storage Temperature Range (F)
-40 F to +158 F
Shipping and Storage Temperature Range (C)
-40 C to +70 C
Approvals, CE
89/336/ECC, 73/23/EEC
Approvals, Canadian Underwriters Laboratories Inc.
cUL C22.2 No. 24-93
Approvals, C-Tick
N314
Environmental, Electrical or Ingress Protection Rating
NEMA 2
Internal Auxiliary Switch
0
Maximum Noise Rating
Driving (dB(A) @ 1m)-- 40; Holding (dB(A) @ 1m)-- 20 (no audible noise)
Stroke
95 ±3 degrees
Shaft Dimensions (in.)
3/8 to 1.06 in. round or 3/8 to 11/16 in. square
Actuator Type
Damper; Valve
Control Signal
Sylk-enabled
Fail Safe Mode
Spring Return
Torque Rating (lb-in.)
175 lb-in.
Torque Rating (Nm)
20 Nm
Spring Return Torque/Force (lb-in., lbf)
175 lb-in.
Spring Return Torque/Force (Nm, N)
20 Nm
Additional Torque Ratings (lb-in.)
Maximum Stall-- 300 lb-in.
Additional Torque Ratings (Nm)
Maximum Stall-- 34 Nm
External Auxiliary Switches Available
Yes, SW2-US
Rotation to Open
By switch
Rotational Stroke Adjustment
Mechanically limited 5 degree increments
Timing, Nominal
Driving @ 60 Hz-- 90 sec
Spring Return Timing
Maximum-- 20 sec
Feedback
Sylk-enabled
Shaft Adapter Type
Self-centering clamping
Manual operation
Manual crank
Shaft Dimensions (mm)
10 to 27 mm round or 10 to 18 mm square
Spring Return Direction
By orientation
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.