Overview
MP909D is used for pneumatic proportional control of variable volume terminal units and small dampers. Available in various operating ranges, for either individual or sequence operation with other actuators. Compatible with all competitors products.
Features
- Rugged ribbed aluminum body.
- Low-friction shaft bearing.
- Close tolerance on operating range and stroke.
- Protected barb connector.
- Versatile mounting and connecting hardware options.
- Positive leakproof seal.
Product Specifications
- Dimensions (in.)
- 6 5/16 in. long ( add 1 in. for shaft ) x 2 13/32 in. diameter
- Dimensions (mm)
- 160 mm long ( add 25 mm for shaft ) x 61 mm diameter
- Maximum Safe Operating Pressure (psi)
- 30 psi
- Maximum Safe Operating Pressure (kPa)
- 207 kPa
- Temperature Range (F)
- 50 F to 140 F
- Temperature Range (C)
- 10 C to 60 C
- Includes
- Actuator only. 3/8 in.-16 Threaded Shaft. No Mounting Bracket or Ball Joint
- Approvals, Underwriters Laboratories Inc.
- Components Recognized: Report R18118
- Operating Humidity Range (% RH)
- 5 to 95% RH
- Actuator Type
- Damper
- Fail Safe Mode
- Spring Return
- Stroke (in.)
- 2.4 in.
- Stroke (mm)
- 61 mm
- Actuator Force
- Low
- Spring Range (psi)
- 3 psi to 8 psi
- Spring Range (kPa)
- 21 kPa to 55 kPa
- Diaphragm Effective Area (sq in.)
- 3 sq in.
- Diaphragm Effective Area (sq cm)
- 19.4 sq cm
- Air connections
- Barbed fitting for 3/32 in. O.D. tubing
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.