Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Replacement actuator, only for use with Spyder and Stryker controllers with integral actuators. This non-spring return direct-coupled actuator provides floating control of VAV units. It provides reliable control for air damper applications with up to 10 sq ft (0.9 sq m) / 44 lb-in. (5 Nm) (seal-less damper blades; air friction-dependent).

Features

  • Declutch for manual adjustment
  • Adjustable mechanical end limits
  • Mountable in any orientation

Product Specifications

Application
HVAC
Dimensions (in.)
7.31 in high x 5.31 in wide x 3.25 in deep
Dimensions (mm)
186 mm high x 135 mm wide x 83 mm deep
Includes
Shaft Adapter
Used With
Spyder and Stryker controllers
Weight (lb)
1.2 lb
Weight (kg)
0.54 kg
Materials
Plastic housing
Item Type
Product
Mounting
Direct Coupled
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL873
Tradeline Value
Tradeline
Electrical Connections
Ribbon with a push on 3-pin connector for Spyder and Stryker controllers
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Supply Voltage
24 Vac +20%, -15%; 24 Vdc
Power Consumption
Driving-- 5 VA
Shipping and Storage Temperature Range (F)
-22 F to +176 F
Shipping and Storage Temperature Range (C)
-30 C to +80 C
Approvals, CE
89/336/ECC, 73/23/EEC
Approvals, Canadian Underwriters Laboratories Inc.
cUL C22.2 No. 24-93
Ambient Temperature Range (F)
-5 F to +122 F
Ambient Temperature Range (C)
-20 C to +50 C
Environmental, Electrical or Ingress Protection Rating
IP20
Internal Auxiliary Switch
0
Maximum Noise Rating
Driving (dB(A) @ 1m)-- 35
Stroke
95 ±3 degrees
Shaft Dimensions (in.)
1/4 to 1/2 in. square or 3/8 to 1/2 in. round
Actuator Type
Damper
Control Signal
Floating
Fail Safe Mode
Non-Spring Return
Torque Rating (lb-in.)
44 lb-in.
Torque Rating (Nm)
5 Nm
Additional Torque Ratings (lb-in.)
Maximum Stall-- 70 lb-in.
Additional Torque Ratings (Nm)
Maximum Stall-- 8 Nm
External Auxiliary Switches Available
No
Rotation to Open
Up to 95 degrees
Rotational Stroke Adjustment
Dual Integral Adjustable Stops
Timing, Nominal
Driving @ 60 Hz-- 90 sec
Shaft Adapter Type
U-bolt clamp
Manual operation
Declutch mechanism
Shaft Dimensions (mm)
6 to 13 mm square or 9 to 13 mm round
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.