Overview

M6410A and M7410F Cartridge Globe Valve Non-Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.

Features

  • Suitable for Excel/IRC system or other controllers providing specified signals.
  • Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.
  • No mounting tools required.
  • Small size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.
  • Visual position indication (red pin).

Product Specifications

Application
HVAC
Dimensions (in.)
2 3/8 in. high x 1 15/16 in. wide x 3 15/16 in. deep
Dimensions (mm)
61 mm high x 49 mm wide x 100 mm deep
Includes
1/2 in. conduit hub
Used With
1/2 inch and 3/4 inch V58XX Globe Valves
Weight (lb)
0.3125 lb
Weight (kg)
0.15 kg
Materials
Low Maintenance Plastic Housing
Item Type
Product
Mounting
Threads onto V58XX valve bonnet
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Flammability Rating UL94V-5V
Electrical Connections
Plenum-rated cable
Operating Humidity Range (% RH)
5 to 95% RH
Supply Voltage
24 Vac +10%, -30%
Power Consumption
Driving-- 0.7 VA
Shipping and Storage Temperature Range (F)
-40 F to +158 F
Shipping and Storage Temperature Range (C)
-40 C to +70 C
Ambient Temperature Range (F)
32 F to 122 F
Ambient Temperature Range (C)
0 C to 50 C
Environmental, Electrical or Ingress Protection Rating
IP42,Class I Insulation (24 Vac)
Internal Auxiliary Switch
0
Fluid Temperature (C)
130 C Maximum
Fluid Temperature (F)
266 F Maximum
Actuator Type
Valve
Control Signal
SPDT; Two position; Floating
Fail Safe Mode
Stays in place
Torque Rating (lb-in.)
40.5 lbf
Torque Rating (Nm)
180 N
Switches
No
Stroke (in.)
1/4 in.
Stroke (mm)
6 mm
Cable
Threaded conduit connector
Timing, Nominal
Driving @ 60 Hz (sec)-- 125 sec
Feedback
No
Manual operation
None (use valve dust cap)
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.