Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

Pneumatic temperature controllers provide proportional control of pneumatic valves and damper actuators in HVAC. Replacement devices are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic temperature controller.

Features

  • Fahrenheit or Celsius scales for all adjustments.
  • Pilot operated for high capacity.
  • Direct Acting (DA) and Reverse Acting (RA) models are available.
  • Adjustable setpoint and throttling ranges.
  • Scales in bold type for high visibility.
  • Replaceable filter cartridge.
  • Single point or averaging elements.

Product Specifications

Application
Remote Bulb Temperature
Airflow Usage
0.011 scfm (5.2 mL/s)
Dimensions (in.)
5 9/16 in. high x 3 1/8 in. wide x 2 11/16 in. deep
Dimensions (mm)
142 mm high x 80 mm wide x 68 mm deep
Maximum Safe Operating Pressure (psi)
30 psi
Maximum Safe Operating Pressure (kPa)
207 kPa
Temperature Range (F)
Element: 230 F, Controller: 150 F
Temperature Range (C)
Element: 110 C, Controller: 66 C
Includes
3/8 x 5 1/4 in. (10 x 133 mm) bulb with 10 in. (254 mm) capillary, integral duct mount
Comments
Scale plate is reversible for F and C applications
Setpoint Temperature Range (C)
-1 C to +66 C
Setpoint Temperature Range (F)
30 F to 150 F
Shipping and Storage Temperature Range (F)
150 F
Shipping and Storage Temperature Range (C)
66 C
Sensor Element
Remote bulb
Throttling Range (F)
Factory set at 10 F with adjustment range of 5 to 25 F (Factory set at 6K with adjustment range of 3 to 15 K)
Action
Direct Acting
Number of Pipes
2
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.