Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

One-pipe, single setpoint, pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Commonly used as discharge controllers for unit ventilators.

Features

  • Rod and tube insertion sensing element.
  • Wide throttling range.
  • Gage tee and tank valve facilitate checking line pressures.

Product Specifications

Application
Low Limit controller
Airflow Usage
0.011 scfm (5.2 mL/s)
Dimensions (in.)
5 7/16 in. high x 1 1/16 in. wide x 2 1/4 in. deep
Dimensions (mm)
138 mm high x 27 mm wide x 57 mm deep
Maximum Safe Operating Pressure (psi)
25 psi
Maximum Safe Operating Pressure (kPa)
170 kPa
Temperature Range (F)
135 F maximum
Temperature Range (C)
57 C maximum
Includes
Fittings for mounting on sheet metal duct. Order restrictor separately.
Mounting
Insertion with locknut on boss of insertion shank
Setpoint Temperature Range (C)
4 C to 60 C
Setpoint Temperature Range (F)
40 F to 140 F
Shipping and Storage Temperature Range (F)
150 F maximum
Shipping and Storage Temperature Range (C)
66 C maximum
Sensor Element
Invar rod and seamless brass tube, 18 3/4 in. (476 mm) long and 11/32 in. (9 mm) diameter; Remote Bulb
Throttling Range (F)
5 F to 35 F
Throttling Range (C)
3 C to 19 C
Action
Direct Acting
Air connections
Barb fittings 1/4 in. (6 mm) poly tubing
Setpoint
Single
Number of Pipes
1
Capacity
Low
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.