Overview
Provide operating control with automatic limit protection for pressure systems up to 300 psi (2068 kPa).
Features
- Use with steam, air, noncombustible gases, or fluids non-corrosive to pressure sensing element.
- Models have snap-acting switching to open or close a circuit on pressure rise.
- Have adjustable differentials.
- Adjustments are made by screws on top of case.
- Mount using 1/4 inch -18 NPT internal pipe threads or surface mount through base of case.
- Ground screw terminal.
Product Specifications
- Application
- Provide control of steam, air, non-combustible gases or non-corrosive fluids
- Dimensions (in.)
- 4 31/32 in. high x 4 1/2 in. wide x 2 3/4 in. deep
- Dimensions (mm)
- 126 mm high x 114 mm wide x 70 mm deep
- Mounting
- 1/4 in. NPT internal thread or surface mount through back of case
- Approvals, Underwriters Laboratories Inc.
- Listed: File No. MP466, Guide No. MBPR
- Approvals, Canadian Standards Association
- Certified: File No. LR1620, Guide No. 400-E-O
- Electrical Connections
- Screw terminals
- Contact Ratings
- 120 Vac Switch Contact-- 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac Switch Contact-- 5.1 AFL, 30.6 ALR, 5.0 A resistive
- Operating Temperature Range (F)
- -35 F to +150 F
- Operating Temperature Range (C)
- -37 C to +66 C
- Approvals, Swiss RE
- Acceptable
- Sensor Element
- Stainless Steel diaphragm
- Operating Range (psi)
- 10 to 150 psi; 225 psi - Maximum Sustained
- Operating Range (kPa)
- 69 to 1034 kPa; 1151 kPa - Maximum Sustained
- Differential Pressure Range (psi)
- 10 to 22 psi
- Differential Pressure Range (kPa)
- 60 to 152 kPa
- Differential Type
- Subtractive
- Switch Operation
- Auto recycle
- Switching Action
- SPDT snap action, make R-W, break R-B on pressure rise
- Pipe Connection
- Main or High Pressure--1/4 in. NPT internal thread
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.