Overview

A proportioning pneumatic humidistat used on one- or two-pipe installations for controlling actuators on valves and dampers in air conditioning systems for humidification or dehumidification control.

Features

  • Durable HP970 series humidistat.
  • Snap-on mounting to backplate.
  • Vertical or horizontal mounting.
  • Backplate has molded air connections; no separate fittings needed.
  • Variety of cover finishes and display styles available.
  • Wide throttling range.

Product Specifications

Application
Humidity
Airflow Usage
0.011 scfm (5.2 mL/s)
Dimensions (in.)
3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
Dimensions (mm)
83 mm high x 51 mm wide x 41 mm deep
Maximum Safe Operating Pressure (psi)
25 psi
Maximum Safe Operating Pressure (kPa)
170 kPa
Temperature Range (F)
45 F to 125 F
Temperature Range (C)
7 C to 52 C
Comments
Order Cover Separately
Shipping and Storage Temperature Range (F)
-30 to +150 F
Shipping and Storage Temperature Range (C)
-34 to +66 C
Action
Reverse Acting
Setpoint
Single
Number of Pipes
1 or 2
Scale Markings
15 to 75% RH
Throttling Range (%RH)
7 to 35% RH