Overview
One- or two-pipe, direct-acting humidity sensor used with RP908/RP920 Controllers to provide proportional control of pneumatic valve or damper actuators in systems requiring humidification or dehumidification control.
Features
- Corrosion resistant materials.
- Simple plug-in air head connections.
- Factory calibrated.
- Continuous relative humidity indication available by using receiver gage.
- Integral or external restriction can be used.
Product Specifications
- Application
- Humidity Sensor
- Airflow Usage
- 0.022 scfm (10.4 mL/s)
- Connections
- Push-on barb for 5/32 in. (4 mm) O.D. tubing
- Dimensions (in.)
- 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
- Dimensions (mm)
- 88 mm high x 51 mm wide x 41 mm deep
- Maximum Safe Operating Pressure (psi)
- 25 psi
- Maximum Safe Operating Pressure (kPa)
- 172 kPa
- Comments
- Order Cover Separately
- Mounting
- Vertical or Horizontal Wall Mounting or Mounted in Duct Sampling Chamber
- Operating Temperature Range (F)
- 125 F Maximum
- Operating Temperature Range (C)
- 52 C Maximum
- Pressure Ratings (psi)
- Output--3 psi to 15 psi; Supply--16 to 21 psi
- Pressure Ratings (kPa)
- Output--21 kPa to 103 kPa; Supply--110-145 kPa
- Action
- Direct Acting
- Number of Pipes
- 1 or 2
- Sensor Range
- 15 to 75% RH
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.