Overview
Depending on the model, current is converted into a linear and proportional output signal of 0-5 Vdc, 0-10 Vdc or 4-20 mA and monitored by a building management controller. These Fast acting current sensors are reliable and extremely easy to install.
Features
- Solid or split core loop-powered current transmitters for 4-20 mA models
- Solid or split core 0-5 or 0-10 Vdc models
- Fast response time
- Integral DIN rail mounting flange
- Easy wiring, polarity sensitive output
- Accepts up to a 350 MCM (17.3 mm) cable
- Operates up to 250 continuous amps
- True RMS versions are available
- RoHS and WEEE Complaint
- Limited 5 Year Warranty.
Product Specifications
- Application
- Excellent choice for new installations requiring load treading (current monitoring)
- Dimensions (in.)
- 2 17/64 in. high x 3 3/8 in. wide x 63/64 in. deep
- Dimensions (mm)
- 58 mm high x 86 mm wide x 25 mm deep
- Weight (lb)
- 0.22 lb
- Weight (kg)
- 0.1 kg
- Frequency
- 30 Hz to 1 kHz
- Approvals, Underwriters Laboratories Inc.
- Approved
- Operating Humidity Range (% RH)
- 0 to 95% RH, non-condensing
- Supply Voltage
- 12 to 30 Vdc
- Operating Temperature Range (F)
- 5 F to 104 F
- Operating Temperature Range (C)
- -15 C to 40 C
- Approvals, CE
- Approved
- Enclosure
- UL94-5V/Burgundy
- Accuracy
- ±0.5%
- Core Type
- Solid
- Supply Current
- 36 mA max
- Maximum Current
- continuous--160 Amps; 320 Amps; 400 Amps: for 6 seconds--200 Amps; 400 Amps; 500 Amps;
- Jumper Settings
- Low; Middle; High
- Output Switch Rating
- 4-20 mA Average True RMS
- Isolation Voltage
- 2200 Vac
- Maximum Load Resistance
- 650 Ohms @ 24 Vdc (Vs-10)/0.02-40.2
- Response Time
- <200 mS
- Aperture Size
- 3/4 in. (19 mm). Accepts up to 350 MCM (17.3 mm) cables.
- Approvals, Environmental Compliance
- RoHS-Directive 2002/95/EC, WEEE-Directive 2002/96/EC
- Current Ratings
- 0-200 Amps; 0-250 Amps; 0-100 Amps
- DIN Rail Size (in.)
- 1-3/8 in.
- DIN Rail Size (mm)
- 35 mm
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.