Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

The Honeywell Lighting Stryker applies proven building automation technology to lighting. The Lighting Stryker sends low-voltage signals to lighting relays and 0-10 volt dimming devices to deliver simple, yet powerful lighting control strategies for energy savings. When used with a TR75 Zio Plus, the Wall Module Configuration Wizard embedded in the Lighting Stryker makes setting up lighting control strategies easy and intuitive. Lighting scenes, switching, smart scheduling, occupancy/ vacancy detection, dimming, daylight harvesting, demand response and task tuning can all be easily configured and adjusted with the TR75 Zio Plus. Installers can set up the system as a standalone lighting control network or integrate to HVAC, security, video and other building automation systems. The Lighting Stryker provides BMS connectivity via BACnet objects for easy integration to WEBs-AX™ or other leading building automation systems.

Features

  • Pre-programmed and Configurable
  • Through WEBs-AX can network multiple zones
  • Configured for 0-10V dimming and switching control
  • Relay output option allows for full “off” of 0-10V systems
  • Zio Smart Scene Selector serves as both configuration tool and scene selector
  • Designed for the HVAC Contractor to install, configure and maintain
  • Easier to install and takes less time to configure than proprietary lighting control systems
  • BMS connectivity via BACnet objects for easy commissioning and integration to Honeywell and other building automation systems

Product Specifications

Application
Pre-programmed low voltage lighting control device designed to accept inputs from occupancy/vacancy sensors, switches, photocells and networks to drive line voltage relays and dimming for energy efficient lighting systems.
Dimensions (in.)
5.45 in. high x 6.85 in. wide x 2.26 in. deep
Dimensions (mm)
138.4 mm high x 174 mm wide x 57.4 mm deep
Comments
Onboard 20 VDC power supply
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL 916
Approvals, Canadian Standards Association
Certified
Operating Humidity Range (% RH)
5 to 95% RH, non-condensing
Application Size
Small to Large
Output Type
Pulse Width Modulation, Floating, Staged On/Off
Compatible With
BACnet. WEBs AX and can Standalone
Power Consumption
5 VA
Voltage
24 Vac with a valid range of 20 to 30 Vac
Operating Temperature Range (F)
-40 F to 150 F
Operating Temperature Range (C)
-40 C to 65.5 C
Shipping and Storage Temperature Range (F)
-40 F to 150 F
Shipping and Storage Temperature Range (C)
-40 C to 65.5 C
Approvals, Federal Communications Commission
FCC Part 15, Subpart B, Class B
Approvals, CE
Approved
Building Management Interface
WEBs AX, TR75 Zio
Network Communications
BACnet
Commissioning Software
Bult-In - Through TR75
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.