Skip Ribbon Commands
Skip to main content
SharePoint
  • Product Info
  • Literature

Overview

C7150 Solid State mixed air sensor is used with Honeywell economizer logic modules and W973 and M7415 to proportion outdoor and return air dampers in economizer systems.

Features

  • Uses thermistor sensing element in ventilation duct systems.
  • Negative temperature coefficient (NTC) causes resistance to decrease as sampled air temperature increases.
  • Resistance change used as in input to control W973 and M7415.
  • Requires no settings or calibration.
  • Mounts on duct surface with four screws (not supplied).

Product Specifications

Application
Temperature Mixed Air Sensor for Duct mixed or discharge air
Dimensions (in.)
2 in. high, 2 1/2 in. wide, 3/4 in. deep
Dimensions (mm)
51 mm high x 64 mm wide x 19 mm deep
Used With
W973 and M7415; W7210, W7212, W7213, W7214, W7215, W7459, W7460
Item Type
Product
Mounting
Mount on a mounting bracket (not included) inside the mixed air or discharge air duct.
Approvals, Underwriters Laboratories Inc.
Component Recognized
Electrical Connections
1/4 in. (6 mm) quick-connect terminals.
Sensor
3000 ohms @ 25C NTC
Operating Temperature Range (F)
40 F to 110 F
Operating Temperature Range (C)
4 C to 43 C
Approvals, CE
Report: GV97-011
Color
Black
Ambient Temperature Range (F)
250 F Maximum
Ambient Temperature Range (C)
121 C Maximum
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.