Overview
Compact flame detector for use with flame safeguard controls with ultraviolet amplifiers.
Features
- Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection.
- Mounts on a 1 in. sighting pipe by using an integral collar.
- Protects the sensing tube with a shield.
- Meets outdoor rain tight requirements of Underwriters Laboratories Inc., NEMA 4 and NEMA 4X.
- Wires in parallel for difficult sighting applications.
- Seals against pressures as high as 5 psi (34.5 kPa) when correctly installed.
- Field-replaceable ultraviolet sensing tube.
Product Specifications
- Application
- Coal fired burners; Gas fired burners; Oil fired burners
- Dimensions (in.)
- 1 1/2 in. diameter x 4 1/8 in. long
- Dimensions (mm)
- 38 mm diameter x 105 mm long
- Used With
- Flame Amplifiers: R7249A, B, R7849A, B, R7749B, R7259, R7290
- Weight (lb)
- 6 oz
- Weight (kg)
- 0.17 kg
- Comments
- Detects ultraviolet radiation in flames
- Mounting
- Integral nut for 1 in. sighting pipe.
- Approvals, Underwriters Laboratories Inc.
- Listed: File No. MP268, Guide No. MCCZ
- Approvals, Canadian Standards Association
- Certified: Master Report LR95329-1
- Electrical Connections
- 2 NEC Class 1 lead wires
- Vibration
- 0.5 G max
- Approvals, Swiss RE
- Acceptable
- Approvals, Factory Mutual
- Approved: Report No. 24181.03
- Ambient Temperature Range (F)
- -40 F to +250 F
- Ambient Temperature Range (C)
- -40 C to +121 C
- NEMA Rating
- NEMA 3 and NEMA 4
- Lead Length (in.)
- 72 in.
- Lead Length (mm)
- 1829 mm
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.