Product Specifications
- Application
- HVAC
- Dimensions (in.)
- 5.55 in high x 3.39 in wide x 2.52 in deep
- Dimensions (mm)
- 141 mm high x 86 mm wide x 64 mm deep
- Includes
- 4074ENY Bag Assembly
- Weight (lb)
- 1.5 lb
- Weight (kg)
- 0.68 kg
- Materials
- Steel plate and Plenum rated plastic
- Mounting
- Direct Coupled
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL873, Plenum Rated
- Customer Special
- Kele
- Electrical Connections
- Screw terminals
- Operating Humidity Range (% RH)
- 5 to 95% RH, non-condensing
- Supply Voltage
- 24 Vac ±20%
- Power Consumption
- Driving-- 2.4 VA
- Shipping and Storage Temperature Range (F)
- 20 F to 130 F
- Shipping and Storage Temperature Range (C)
- -18 C to +54 C
- Approvals, Canadian Underwriters Laboratories Inc.
- cUL C22.2 No. 24-93
- Ambient Temperature Range (F)
- 20 F to 125 F
- Ambient Temperature Range (C)
- -18 C to +50 C
- Environmental, Electrical or Ingress Protection Rating
- NEMA 1
- Internal Auxiliary Switch
- 0
- Maximum Noise Rating
- Driving (dB(A) @ 1m)-- 45
- Stroke
- 90 degrees
- Shaft Dimensions (in.)
- 3/8 to 1/2 in. square or round
- Actuator Type
- Damper
- Control Signal
- Floating; SPDT; On/Off
- Fail Safe Mode
- Non-Spring Return
- Torque Rating (lb-in.)
- 70 lb-in.
- Torque Rating (Nm)
- 8 Nm
- Additional Torque Ratings (lb-in.)
- Maximum Stall-- 130 lb-in.
- Additional Torque Ratings (Nm)
- Maximum Stall-- 15 Nm
- External Auxiliary Switches Available
- Yes, 201052B
- Rotation to Open
- By wiring
- Rotational Stroke Adjustment
- Mechanically limited at 45 or 60 degrees in CW or CCW directions
- Timing, Nominal
- Driving @ 60 Hz-- 90 sec
- Feedback
- With accessory
- Shaft Adapter Type
- Aluminum Hub, two set screws
- Manual operation
- Declutch mechanism
- Shaft Dimensions (mm)
- 10 to 13 mm square/round
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.