Privacy Statement
Skip Ribbon Commands
Skip to main content
SharePoint
Item 6 Of 6
Fan Coil Thermostat,2 pipe Rem.Heat/Cool

T6069D4014/U

Fan Coil Degree F T-Stat, 2 Pipe Heat/ Cool, Constant or Cycled Fan,44-86F. with Thermometer. Tan Color

  • Product Info
  • Literature
  • Accessories & Replacement Parts

Overview

T6069 thermostats control line voltage valves and/or blower motors on fan coil units in manual changeover heating/cooling systems. The thermostats feature a single System and Fan speed switch.

Features

  • Thermostat, system and fan control switches combined in one deluxe-styled unit.
  • Available in classic gold or contemporary white styling. Language-free graphic symbols.
  • Manual three-speed fan control on most models.
  • Suitable for single or double gang electrical boxes.
  • Operates one or two valves.
  • Has cycled or constant fan control.

Product Specifications

Hazmat Information
UN 2037, RECEPTACLES, SMALL, CONTAINING GAS, 2.1
Application
2 pipe fan coil, seasonal auto changeover, constant or cycled fan
Dimensions (in.)
4 5/8 in. high x 4 1/2 in. wide x 1 7/8 in. deep. + 5/8 in projection into junction box
Dimensions (mm)
117 mm high x 114 mm wide x 47 mm deep + 15 mm projection into junction box
Item Type
Product
Mounting
Mounts on 2 in. x 4 in. (50mm x 75 mm) single or double-ganged vertically-oriented outlet box.
Electrical Ratings
8.0 AFL / 48 ALR / 13A resistive @ 120 Vac; 4.4 AFL / 26.4 ALR / 7.5A resistive @208 Vac; 4.0 AFL / 24 ALR / 6.5A resistive @240 Vac; 3.3 AFL / 19.8 ALR 5.5A resistive @277 Vac
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
File No. E4436, Guide No. XAPX
Approvals, Canadian Standards Association
File No. LR1322
Supply Voltage
120 to 277 Vac
Switch Positions (System)
ON-AUTO-OFF
Switch Positions (Fan)
HI-MED-LO
Differential Temperature (F)
2 F
Color
Tan
Display
Thermometer Included
Changeover
Seasonal Auto with External Aquastat® Controller
Setting Temperature Range (F)
44 F to 86 F

Accessories

TG511A1000/U

Med. univ. thermostat guard Clear cover

TG511D1004/U

Med. univ. thermostat guard Beige cover