Skip Ribbon Commands
Skip to main content
SharePoint
Item 1 Of 1
Return Air Temperature Controller(Industrial Live Volt Thermostat),-30F to 110F, Tin Plated Element

T6054A1005/U

Return Air Temperature Controller(Industrial Live Volt Thermostat),-30F to 110F, Tin Plated Element

  • Product Info
  • Literature

Overview

Provides SPDT heavy-duty, line-voltage temperature control in ventilation, heating or cooling systems.

Features

  • Use in a variety of farm, industrial or commercial applications.
  • Wall or duct mount in any position.
  • Fast response, tin-plated element not affected by adverse environment.
  • Rugged case.
  • Mounts on flat surface with three screws.

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
Provides control in ventilation, heating, cooling or heating-cooling systems
Dimensions (in.)
7 1/4 in. high x 2 5/8 in. wide x 2 in. deep
Dimensions (mm)
184 mm high x 67 mm wide x 51 mm deep
Includes
Case
Item Type
Product
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Listed: E4436, vol. 5, sec. 12, Guide XAPX
Approvals, Canadian Standards Association
CSA Listed: Report -1
Tradeline Value
Tradeline
Contact Ratings
120 Vac-- 7.4 AFL, 44.4 ALR; 240 Vac-- 3.7 AFL, 22.2 ALR
Voltage
120 Vac; 240 Vac
Setpoint Temperature Range (C)
-34 C to +43 C
Setpoint Temperature Range (F)
-30 F to +110 F
Operating Temperature Range (F)
125 F Maximum
Operating Temperature Range (C)
52 C Maximum
Output
relay
Relay Outputs
1 SPDT
Sensor Inputs
1
Sensor Element
Copper filled element
Accuracy (F)
±10 F
Accuracy (C)
±5.6 C
Differential Temperature (F)
3.5 F
Differential Temperature (C)
1.9 C
Color
Gray